Table 10 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
OPT2 UNIT OPTIONS 2 CONTROLS
CTRL X CONTROL METHOD Default: Switch
0 = Enable/Off/Remote Switch
2 = Occupancy
3 = CCN Control
LOAD X LOADING SEQUENCE SELECT Default: Equal
1 = Equal
2 = Staged
LLCS X LEAD/LAG CIRCUIT SELECT Default: Automatic
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT XX.X F HIGH LCW ALERT LIMIT
Default: 60
Range: 2 to 60 F
DELY XX MINUTES OFF TIME
Default: 0 Minutes
Range: 0 to 15 Minutes
ICE.M ENBL/DSBL ICE MODE ENABLE Default: Disable
LS.MD X LOW SOUND MODE SELECT Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
LS.ST 00:00 LOW SOUND START TIME Default: 00:00
LS.ND 00:00 LOW SOUND END TIME Default: 00:00
LS.LT XXX % LOW SOUND CAPACITY LIMIT
Default: 100%
Range: 0 to 100%
CCN CCN NETWORK CONFIGURATION
CCNA XXX CCN ADDRESS
Default: 1
Range: 1 to 239
CCNB XXX CCN BUS NUMBER
Default: 0
Range: 0 to 239
BAUD X CCN BAUD RATE Default: 9600
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
HP.A HEAD PRESSURE CMP DELTA
A1.DT XX SCT DELTA FOR COMP A1 Range: 0 - 50 Default: 12
A2.DT XX
SCT DELTA FOR COMP A2 Range: 0 - 50 Default: 12
HP.B HEAD PRESSURE CMP DELTA
B1.DT XX SCT DELTA FOR COMP B1 Range: 0 - 50 Default: 12
B2.DT XX
SCT DELTA FOR COMP B2 Range: 0 - 50 Default: 12