Carrier 30RAP010-060 Air Conditioner User Manual


 
6
Table 3 — Run Status Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
ITEM
EXPANSION
COMMENT
VIEW EWT XXX.X F ENTERING FLUID TEMP
LWT XXX.X F LEAVING FLUID TEMP
SETP XXX.X F ACTIVE SETPOINT
CTPT XXX.X F CONTROL POINT
LOD.F XXX LOAD/UNLOAD FACTOR
STAT X CONTROL MODE 0 = Service Test
1 = Off Local
2 = Off CCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On CCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
LD.PM LEAD PUMP
OCC YES/NO OCCUPIED
LS.AC YES/NO LOW SOUND ACTIVE
MODE YES/NO OVERRIDE MODES IN EFFECT
CAP XXX % PERCENT TOTAL CAPACITY
STGE X REQUESTED STAGE
ALRM XXX CURRENT ALARMS & ALERTS
TIME XX.XX TIME OF DAY 00.00-23.59
MNTH XX MONTH OF YEAR 1 = January, 2 = February, etc.
DATE XX DAY OF MONTH 01-31
YEAR XX YEAR OF CENTURY
RUN HRS.U XXXX HRS MACHINE OPERATING HOURS
STR.U XXXX MACHINE STARTS
HR.P1 XXXX.X PUMP 1 RUN HOURS
HR.P2 XXXX.X PUMP 2 RUN HOURS
HOUR HRS.A XXXX HRS CIRCUIT A RUN HOURS
HRS.B XXXX HRS CIRCUIT B RUN HOURS See Note
HR.A1 XXXX HRS COMPRESSOR A1 RUN HOURS
HR.A2 XXXX HRS COMPRESSOR A2 RUN HOURS
HR.B1 XXXX HRS COMPRESSOR B1 RUN HOURS See Note
HR.B2 XXXX HRS COMPRESSOR B2 RUN HOURS See Note
STRT ST.A1 XXXX COMPRESSOR A1 STARTS
ST.A2 XXXX COMPRESSOR A2 STARTS
ST.B1 XXXX COMPRESSOR B1 STARTS See Note
ST.B2 XXXX COMPRESSOR B2 STARTS See Note
PM PUMP PUMP MAINTENANCE
SI.PM XXXX HRS PUMP SERVICE INTERVAL Default: 8760
P.1.DN XXXX HRS PUMP 1 SERVICE COUNTDOWN
P.2.DN XXXX HRS PUMP 2 SERVICE COUNTDOWN
P.1.MN YES/NO PUMP 1 MAINTENANCE DONE User Entry
P.2.MN YES/NO PUMP 2 MAINTENANCE DONE User Entry
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER