Table 4 — Service Test Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
TEST ON/OFF SERVICE TEST MODE To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
OUTS OUTPUTS AND PUMPS
EXV.A 0 to 100% EXV A % OPEN
EXV.B 0 to 100% EXV B % OPEN
FAN1 ON/OFF FAN 1 RELAY
FAN2 ON/OFF FAN 2 RELAY
FAN3 ON/OFF FAN 3 RELAY
FAN4 ON/OFF FAN 4 RELAY
FAN5 ON/OFF FAN 5 RELAY
FAN6 ON/OFF FAN 6 RELAY
V.HPA 0 to 100% VAR HEAD PRESS %
V.HPB 0 to 100% VAR HEAD PRESS %
CLP.1 ON/OFF COOLER PUMP 1 RELAY
CLP.2 ON/OFF COOLER PUMP 2 RELAY
UL.TM 0 to 15 COMP A1 UNLOAD TIME
CL.HT ON/OFF COOLER/PUMP HEATER
RMT.A ON/OFF REMOTE ALARM RELAY
CMPA CIRCUIT A COMPRESSOR TEST
CC.A1 ON/OFF COMPRESSOR A1 RELAY
UL.TM 0 to 15 COMP A1 UNLOAD TIME
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
MLV ON/OFF MINIMUM LOAD VALVE RELAY
CMPB CIRCUIT B COMPRESSOR TEST See Note
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY