CL-8
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘MM’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
RSET (Reset Configuration Settings)
PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
SLCT (Setpoint and Ramp Load Configuration)
SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY
RSET RESET COOL TEMP
CRST COOLING RESET TYPE X
MA.DG 4-20 - DEGREES RESET XX.X °F
RM.NO REMOTE - NO RESET TEMP XXX.X °F
RM.F REMOTE - FULL RESET TEMP XXX.X °F
RM.DG REMOTE - DEGREES RESET XX.X °F
RT.NO RETURN - NO RESET TEMP XXX.X °F
RT.F RETURN - FULL RESET TEMP XXX.X °F
RT.DG RETURN - DEGREES RESET XX.X °F
DMDC DEMAND LIMIT SELECT X
DM20 DEMAND LIMIT AT 20 MA XXX %
SHNM LOADSHED GROUP NUMBER XXX
SHDL LOADSHED DEMAND DELTA XXX %
SHTM MAXIMUM LOADSHED TIME XXX
DLS1 DEMAND LIMIT SWITCH 1 XXX %
DLS2 DEMAND LIMIT SWITCH 2 XXX %
LLEN LEAD/LAG CHILLER ENABLE ENBL/DSBL
MSSL MASTER/SLAVE SELECT SLVE/MAST
SLVA SLAVE ADDRESS XXX
LLBL LEAD/LAG BALANCE SELECT X
LLBD LEAD/LAG BALANCE DELTA XXX
LLDY LAG START DELAY XXX
PARA PARALLEL CONFIGURATION YES/NO
SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY
SLCT SETPOINT AND RAMP LOAD
CLSP COOLING SETPOINT SELECT X
RL.S RAMP LOAD SELECT ENBL/DSBL
CRMP COOLING RAMP LOADING X.X
SCHD SCHEDULE NUMBER XX
Z.GN DEADBAND MULTIPLIER X.X