Carrier 30RAP010-060 Air Conditioner User Manual


 
71
Table 42 — Alarm and Alert Codes (cont)
LEGEND FOR TABLE 42
COMPRESSOR FAILURE ALERTS
T051, T052 (Circuit A Compresser Failures)
T055, T056 (Circuit B Compressor Failures) — Alert codes
051, 052, 055, and 056 are for compressors A1, A2, B1, and
B2 respectively. These alerts occur when the current sensor
(CS) does not detect compressor current during compressor op-
eration. When this occurs, the control turns off the compressor.
If the current sensor board reads OFF while the compressor
relay has been commanded ON, an alert is generated.
POSSIBLE CAUSES
Compressor Overload
— Either the compressor internal over-
load protector is open or the external overload protector (Kri-
wan module) has activated. The external overload protector
modules are mounted in the compressor wiring junction box.
Temperature sensors embedded in the compressor motor wind-
ings are the inputs to the module. The module is powered with
24 vac from the units main control box. The module output is a
normally closed contact that is wired in series with the com-
pressor contactor coil. In a compressor motor overload condi-
tion, contact opens, deenergizing the compressor contactor.
Low Refrigerant Charge
— If the compressor operates for an
extended period of time with low refrigerant charge, the com-
pressor ASTP device will open, which will cause the compres-
sor to trip on its overload protection device.
Circuit Breaker Trip
— The compressors are protected from
short circuit by a breaker in the control box.
Wiring Error
— A wiring error might not allow the compres-
sor to start.
To check out alerts T051-T056:
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely
the problem is one of the following: HPS open, open in-
ternal protection, circuit breaker trip, incorrect safety wir-
ing, or incorrect compressor wiring.
2. If the compressor does start, verify it is rotating in the cor-
rect direction.
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
T302 Alert
Strainer Blowdown
Scheduled
Maintenance Due
Strainer Service
Countdown (S.T.DN)
expired. Complete strainer
blowdown and enter 'YES'
for Strainer Maintenance
Done (S.T.MN) item.
None Automatic
Routine strainer
maintenance
required
T303 Alert
Condenser Coil
Maintenance Due
Coil Service Countdown
(C.L.DN) expired.
Complete condenser coil
cleaning and enter 'YES'
for Coil Maintenance Done
(C.L.MN) item.
None Automatic
Routine condenser
coil maintenance
required
T500 Alert
Current Sensor Board
A1 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor A1 shut
down
Automatic
CSB failure.
Wiring error.
T501 Alert
Current Sensor Board
A2 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor A2 shut
down
Automatic
CSB failure.
Wiring error.
T502 Alert
Current Sensor Board
A3 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor A3 shut
down
Automatic
CSB failure.
Wiring error.
T503 Alert
Current Sensor Board
B1 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor B1 shut
down
Automatic
CSB failure.
Wiring error.
T504 Alert
Current Sensor Board
B2 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor B2 shut
down
Automatic
CSB failure.
Wiring error.
T505 Alert
Current Sensor Board
B3 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor B3 shut
down
Automatic
CSB failure.
Wiring error.
T950 Alert Loss of Communication
with Water System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
WSM forces removed.
Chiller runs under own
control
Automatic Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
T951 Alert Loss of Communication
with Chillervisor System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
CSM forces removed.
Chiller runs under own
control
Automatic Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
T952 Alert Loss of Communication
with Hydronic System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
HSM forces removed.
Chiller runs under own
control
Automatic Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
CCN Carrier Comfort Network
CSB Current Sensor Board
EEPROM — Electronic Eraseable Programmable Read Only Memory
EMM Energy Management Module
EWT Entering Fluid Temperature
EXV Electronic Expansion Valve
HSM Hydronic System Manager
LCW Leaving Chilled Water
LWT Leaving Fluid Temperature
MBB Main Base Board
OAT Outdoor-Air Temperature
SCT Saturated Condensing Temperature
WSM Water System Manager
IMPORTANT: Prolonged operation in the wrong direction
can damage the compressor. Correct rotation can be veri-
fied by a gage set and looking for a differential pressure
rise on start-up.