APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
EXV.A
CIR A EXV CONFIGURATION
STR.A XXX EXV CIrc.A Start Pos
Default: 50
0 to 100
MIN.A XXX EXV Circ.A Min Position
Default: 8
0 to 100
RNG.A XXXXX EXVA Steps In Range 0 to 65535
SPD.A XXXXX EXVA STeps Per Second
Default: 200
0 to 65535
POF.A XXX EXVA Fail Position In %
Default: 0
0 to 100
MIN.A XXXXX EXVA Minimum Steps
Default: 0
0 to 65535
MAX.A XXXXX EXVA Maximum Steps 0 to 65535
OVR.A XXX EXVA Overrun Steps
Default: 167
0 to 65535
TYP.A 0,1 EXVA Stepper Type
Default: 1
0 = UNIPOLAR
1 = BIPOLAR
H.SCT XXX High SCT Threshold
Default: 115
50 to 140
X.PCT XX Open EXV X% On 2nd Comp
Default: 10
0 to 30
X.PER XX Move EXV X% On DISCRSOL
Default: 5
0 to 30
A.PCT XXX Pre-open EXV - Fan Adding
Default: 10
0 to 100
M.PCT XXX Pre-close EXV - Fan Sub
Default: 10
0 to 100
S.PCT XXX Pre-close EXV - Lag Shut
Default: 10
0 to 100
DELY XXX Lag Start Delay
Default: 10
0 to 100
EXV.B
CIR B EXV CONFIGURATION
STR.B XXX EXV CIrc.B Start Pos
Default: 50
0 to 100
MIN.B XXX EXV Circ.B Min Position
Default: 8
0 to 100
RNG.B XXXXX EXVB Steps In Range 0 to 65535
SPD.B XXXXX EXVB STeps Per Second
Default: 200
0 to 65535
POF.B XXX EXVB Fail Position In %
Default: 0
0 to 100
MIN.B XXXXX EXVB Minimum Steps
Default: 0
0 to 65535
MAX.B XXXXX EXVB Maximum Steps 0 to 65535
OVR.B XXX EXVB Overrun Steps
Default: 167
0 to 65535
TYP.B 0,1 EXVB Stepper Type
Default: 1
0 = UNIPOLAR
1 = BIPOLAR