APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — CIRB_EXV
CCN MAINTENANCE TABLES — STRTHOUR
CCN MAINTENANCE TABLES — CURRMODS
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
EXV % Open nnn % EXV_B
Circuit B Approach nnn.n delta F CIRB_APP
Approach Setpoint nnn.n delta F APPRB_SP
EXVB Override nnnnn EXVBOVRR
Suction Superheat Temp nnn.n delta F SH_B
Active Superheat Setpt nn.n delta F ACTSH_SP
Active MOP Setpt nn.n delta F ACMOP_SP
Cir B EXV Position Limit nnn % PLMB
DESCRIPTION VALUE UNITS POINT NAME
Machine Operating Hours nnnnnn hours HR_MACH
Machine Starts nnnnnn CY_MACH
Circuit A Run Hours nnnnnn hours HR_CIRA
Compressor A1 Run Hours nnnnnn hours HR_A1
Compressor A2 Run Hours nnnnnn hours HR_A2
Circuit B Run Hours nnnnnn hours HR_CIRB
Compressor B1 Run Hours nnnnnn hours HR_B1
Compressor B2 Run Hours nnnnnn hours HR_B2
Circuit A Starts nnnnnn CY_CIRA
Compressor A1 Starts nnnnnn CY_A1
Compressor A2 Starts nnnnnn CY_A2
Circuit B Starts nnnnnn CY_CIRB
Compressor B1 Starts nnnnnn CY_B1
Compressor B2 Starts nnnnnn CY_B2
PUMP HOURS
Pump 1 Run Hours nnnnnn hours HR_PUMP1
Pump 2 Run Hours nnnnnn hours HR_PUMP2
DESCRIPTION VALUE POINT NAME
CSM controlling Chiller On/Off MODE_1
WSM controlling Chiller On/Off MODE_2
Master/Slave control On/Off MODE_3
Ramp Load Limited On/Off MODE_5
Timed Override in effect On/Off MODE_6
Low Cooler Suction TempA On/Off MODE_7
Low Cooler Suction TempB On/Off MODE_8
Slow Change Override On/Off MODE_9
Minimum OFF time active On/Off MODE_10
Dual Setpoint On/Off MODE_13
Temperature Reset On/Off MODE_14
Demand/Sound Limited On/Off MODE_15
Cooler Freeze Protection On/Off MODE_16
Low Temperature Cooling On/Off MODE_17
High Temperature Cooling On/Off MODE_18
Making ICE On/Off MODE_19
Storing ICE On/Off MODE_20
High SCT Circuit A On/Off MODE_21
High SCT Circuit B On/Off MODE_22
Minimum Comp. On Time On/Off MODE_23
Pump Off Delay Time On/Off MODE_24
Low Sound Mode On/Off MODE_25