Carrier 30RAP010-060 Air Conditioner User Manual


 
79
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
DISP
DISPLAY CONFIGURATION
TEST ON/OFF Test Display LEDs
METR ON/OFF Metric Display Off = English On = Metric
LANG X Language Selection
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
PAS.E ENBL/DSBL Password Enable
PASS XXXX Service Password
UNIT
UNIT CONFIGURATION
SIZE Unit Size
SZA.1 XX Compressor A1 Size
SZA.2 XX Compressor A2 Size
SZA.3 XX Compressor A3 Size
SZA.4 XX Compressor A4 Size
SZB.1 XX Compressor B1 Size
SZB.2 XX Compressor B2 Size
SZB.3 XX Compressor B3 Size
SZB.4 XX Compressor B4 Size
SH.SP XX Suction Superheat Setpt
FAN.S X Number of Fans Default: 5
EXV YES/NO EXV Module Installed
A1.TY YES/NO Compressor A1 Digital Default: No
MAX.T XX Maximum A1 Unload Time
Default: 7
Max = 12 (010,015)
Max = 10 (018-060)
OPT1
UNIT OPTIONS 1 HARDWARE
FLUD X Cooler Fluid Default: Water
1 = Water
2 = Medium Temperature Brine
MLV.S YES/NO Minimum Load Valve Select
CSB.E ENBL/DSBL Csb Boards Enable Default: Enable
CPC ON/OFF Cooler Pump Control Default: Off
PM1E YES/NO Cooler Pump 1 Enable
PM2E YES/NO Cooler Pump 2 Enable
PM.P.S YES/NO Cooler Pmp Periodic Strt Default: No
PM.SL X Cooler Pump Select Default: Automatic
0 = Automatic
1 = Pump 1 Starts first
2 = Pump 2 Starts first
PM.DY XX MIN Cooler Pump Shutdown Dly 0 to 10 minutes, Default: 1 min.
PM.DT XXXX HRS Pump Changeover Hours Default: 500 hours
ROT.P YES/NO Rotate Cooler Pumps Now User Entry
EMM YES/NO EMM Module Installed
CND.T X Cnd HX Typ:0=RTPF 1=MCHX
MOPS XX EXV MOP Set Point
APPR XX Config Approach Set Point