APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs)
CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Parameters)
CCN DISPLAY TABLES — CIRCBDIO (Circuit B Discrete Inputs/Outputs)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRC. A DISCRETE OUTPUTS
Compressor A1 Relay On/Off K_A1_RLY N
Compressor A2 Relay On/Off K_A2_RLY N
Minimum Load Valve Relay On/Off MLV_RLY N
CIRC. A DISCRETE INPUTS
Compressor A1 Feedback On/Off K_A1_FBK N
Compressor A2 Feedback On/Off K_A2_FBK N
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRCUIT B ANALOG VALUES
Percent Total Capacity 0-100 % CAPB_T N
Percent Available Cap. 0-100 % CAPB_A N
Discharge Pressure nnn.n PSIG DP_B N
Suction Pressure nnn.n PSIG SP_B N
Head Setpoint nnn.n °F HSP N
Saturated Condensing Tmp snnn.n FTMP_SCTBN
Saturated Suction Temp snnn.n F TMP_SSTB N
EXV % Open nnn % EXV_B N
Var Head Press Output nnn.n milliamps VHP_ACT N
Compr Return Gas Temp nnn.n FTMP_RGTBN
Suction Superheat Temp nnn.n FSH_BN
Spare 2 Temperature nnn.n °F SPR2_TMP N
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRC. B DISCRETE OUTPUTS
Compressor B1 Relay On/Off K_B1_RLY N
Compressor B2 Relay On/Off K_B2_RLY N
Minimum Load Valve Relay On/Off MLV_RLY N
CIRC. B DISCRETE INPUTS
Compressor B1 Feedback On/Off K_B1_FBK N
Compressor B2 Feedback On/Off K_B2_FBK N