95
APPENDIX B — CCN TABLES (cont)
CCN SERVICE TABLES — SERVICE
CCN SETPOINT TABLES — SETPOINT
CCN MAINTENANCE TABLES — CIRA_EXV
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
SERVICE
Brine Freeze Point nnn.n F BRN_FRZ
Pump Service Interval nnnnn hours SI_PUMPS
COMPRESSOR ENABLE
Enable Compressor A1 Disable/Enable ENABLEA1
Enable Compressor A2 Disable/Enable ENABLEA2
Enable Compressor B1 Disable/Enable ENABLEB1
Enable Compressor B2 Disable/Enable ENABLEB2
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
COOLING
Cooling Setpoint 1 –20 to 70 44.0 FCSP1
Cooling Setpoint 2 –20 to 70 44.0 FCSP2
ICE Setpoint –20 to 32 32.0 FCSP3
RAMP LOADING
Cooling Ramp Loading 0.2 to 2.0 1.0 CRAMP
Brine Freeze Point –20 to 34 34.0 F BRN_FRZ
Head Setpoint FHSP
Fan On Set Point F FANONSP
Fan Off Set Point FFANOFFSP
Fan Stage Delta FFSTGDLTA
Base Fan Off Delta Temp FB_FANOFF
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
EXV % Open nnn % EXV_A
Circuit A Approach nnn.n delta F CIRA_APP
Approach Setpoint nnn.n delta F APPRA_SP
EXVA Override nnnnn EXVAOVRR
Suction Superheat Temp nnn.n delta F SH_A
Active Superheat Setpt nn.n delta F ACTSH_SP
Active MOP Setpt nn.n delta F ACMOP_SP
Cir A EXV Position Limit nnn % PLMA