Connection to the stand-alone option
1
WIRING
1.6.5 Connection of the power regeneration common
converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the
inverter terminals (P/+, N/-) and power regeneration common converter (FR-CV)
terminals as shown below so that their symbols match with each other.
*1. Always keep the power input terminals R/L1, S/L2, T/L3 open. Incorrect connection
will damage the inverter.
*2. Do not insert an MCCB between the terminals P/+-N/- (between P/L+-P/+, between
N/L--N/-). Opposite polarity of terminals N/-, P/+ will damage the inverter.
*3. Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals used
for the MRS, RES signal.
*4. Always connect the power supply and terminals R/L11, S/L21, T/MC1.
Operating the inverter without connecting them will damage the power regeneration
common converter.
*5. Be sure to connect terminal RDYB of the FR-CV to the MRS signal assigned terminal
of the inverter, and connect terminal SE of the FR-CV to terminal SD of the inverter.
Without proper connecting, FR-CV will be damaged.
CAUTION
The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1, S2/
L2, T2/L3 must be matched.
Use sink logic (factory setting) when the FR-CV is connected. The FR-CV
cannot be connected when source logic is selected.
Do not remove a jumper across terminal P/+ and P1.
Do not connect the filter pack.
R/L11
Dedicated stand-alone
reactor (FR-CVL)
S/L
21
T/L31
R2/L12
S2/L22
T2/L32
R2/L1
S2/L2
T2/L3
R/L11
S/L21
T/MC1
P/L+
U
V
W
IM
FR-CV type power
regeneration common converter
Inverter
PC
SD
MRS
RES
SD
P24
SD
RDYB
RSO
SE
RDYA
N/L-
*2
*4
R/L1
S/L2
T/L3
P/+
N/-
*1
Three-phase
A
C power supply
MCCB
MC
1
*3
*3
*5