A-2
2. Fire Prevention
3. Injury Prevention
4. Additional Instructions
Also note the following points to prevent an accidental failure, injury, electric shock,
etc.
(1) Transportation and installation
CAUTION
zInstall the inverter (filter pack) on an incombustible wall without holes, etc.
Mounting it to or near combustible material can cause a fire.
zIf the inverter has become faulty, switch off the inverter power. A continuous flow of
large current could cause a fire.
z
Do not connect the resistor directly to the DC terminals P and N. This coule cause a fire.
CAUTION
zApply only the voltage specified in the instruction manual to each terminal to
prevent damage, etc.
zAlways connect to the correct terminal to prevent damage, etc.
zAlways make sure that polarity is correct to prevent damage, etc.
zWhile power is on or for some time after power-off, do not touch the inverter (filter
pack) or break register as they are hot and you may get burnt.
CAUTION
zWhen carrying products, use correct lifting gear to prevent injury.
zDo not stack the inverter boxes higher than the number recommended.
zEnsure that installation position and material can withstand the weight of the
inverter. Install according to the information in the instruction manual.
zDo not install or operate if the inverter (filter pack) is damaged or has parts missing.
zWhen carrying the inverter, do not hold it by the front cover or setting dial; it may fall
off or fail.
zDo not stand or rest heavy objects on the inverter.
zCheck the inverter mounting orientation is correct.
zPrevent other conductive bodies as screws and metal fragments or other
flammable substance as oil from entering the inverter (filter pack).
zAs the inverter (filter pack) is a precision instrument, do not drop or subject it to impact.
zUse the inverter under the following environmental conditions: This could cause the
inverter (filter pack) damage.
*1 Temperatures applicable for a short time, e.g. in transit.
*2 When using with the filter pack installed on the rear panel of the FR-F520J-15K or
FR-F540J-15K, do not install this combination on moving objects or places that
have vibrations exceeding 1.96m/s
2
.
Environment
Surrounding Air
Temperature
-10°C to +50°C (non-freezing)
Ambient
humidity
90%RH maximum (non-condensing)
Storage
temperature
-20°C to +65°C *1
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist,
dust and dirt)
Altitude/
vibration
Max.1000m above sea level 5.9m/s
2