Mitsubishi Electronics 520 540 Air Conditioner User Manual


 
102
Restart operation
2.6.3 Monitoring reference (Pr. 55 , Pr. 56 )
<Setting>
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 54 "FMterminal function selection" = "0" and Pr. 56 is set when
Pr. 54 = "1".
Set the Pr. 55 and Pr. 56 values so that the output pulse train output of terminal FM is
1440 pulses/s.
2.7 Restart operation
2.7.1 Restart setting (Pr. 57 , Pr. 58 )
Set the frequency
or current which
is referenced
when the output
frequency or
output current is
selected for the
terminal FM.
Parameter Name Factory Setting
Setting
Range
Remarks
55
Frequency monitoring
reference
60Hz 0 to 120Hz
Setting is enabled when
Pr. 30 = "1"
56
Current monitoring
reference
Rated inverter
current
0 to 100A
CAUTION
The maximum pulse train output of terminal FM is 2400 pulses/s. If Pr. 55 is not
adjusted, the output of terminal FM will be filled to capacity. Therefore, adjust
Pr. 55.
At power restoration after an instantaneous power failure, you can restart the
inverter without stopping the motor (with the motor coasting).
Parameter Name
Factory
Setting
Setting
Range
Remarks
57 Restart coasting time - - -
0 to 5s,
- - -
Setting is enabled when Pr. 30 = "1"
58 Restart cushion time 1s 0 to 60s
Output
frequency
Pr.55
Output
frequency
Pr.56
Output or display
Output or display
1440 pulses/s (terminal FM)
1440 pulses/s (terminal FM)