Mitsubishi Electronics 520 540 Air Conditioner User Manual


 
165
Parameter unit (FR-PU04) setting
2
FUNCTIONS
<Setting>
* The monitor display and the are valid.
n17 Setting Disconnected PU Detection PU Setting Lock*
0
Operation is continued as-is if the PU is disconnected
(without disconnected PU detection)
Parameter unit (FR-
PU04) is valid
1
Inverter output is shut off when the PU is disconnected
(with disconnected PU detection)
10
Operation is continued as-is if the PU is disconnected
(without disconnected PU detection)
Operation panel is
valid
CAUTION
The motor decelerates to a stop when the PU is disconnected during PU jog
operation with n17 set to any of "0, 10" (operation is continued if the PU is
disconnected).
REMARKS
When RS-485 communication operation is performed through the RS-485 connector, the reset
selection/PU stop selection function is valid but the disconnected PU detection function is
invalid.
CAUTION
Do not reset the inverter while the start signal is being input.
Doing so will cause the inverter to start immediately after a reset, leading to
hazardous conditions.
STOP
RESET