Mitsubishi Electronics 520 540 Air Conditioner User Manual


 
173
Errors (Alarms)
3
PROTECTIVE FUNCTIONS
(2) Minor failures
When the protective function is activated, the output is not shut off. You can make
parameter setting to output the minor fault signal. (Set "98" in any of Pr. 64, Pr. 65
(output terminal function selection). Refer to page 111.)
Operation Panel Indication
PE FR-PU04 Corrupt Memory
Name Parameter storage device alarm
Description
A fault occurred in parameters stored
(example: EEPROM fault).
Check point
Check for too many number of parameter write times.
Corrective action
Please contact your sales representative.
Operation Panel Indication
PUE FR-PU04 PU Leave Out
Name Parameter Unit disconnection
Description
Stops the inverter output if communication between inverter and
PU is suspended, e.g. if the PU is disconnected with "1" set in the
communication parameter n17 "disconnected PU detection/PU
setting lock".
Check point
Check that the FR-PU04 is fitted securely.
Check the setting of the communication parameter n17
"disconnected PU detection".
Corrective action Fit the FR-PU04 securely.
Operation Panel Indication
RET FR-PU04 Retry No Over
Name
Retry count over
Description
If operation cannot be resumed properly within the number of
retries set, this function stops the inverter output.
Check point Find the cause of alarm occurrence.
Corrective action Eliminate the cause of the error preceding this error indication.
Operation Panel Indication
CPU FR-PU04 CPU Fault
Name
CPU error
Description
If the arithmetic operation of the built-in CPU does not end within a
predetermined period, the inverter self-determines it as an alarm
and stops the output.
Check point
Corrective action
Please contact your sales representative.
Operation Panel Indication
FN FR-PU04 FN
Name Fan trouble
Description
For the inverter which contains a cooling fan, appears on the
operation panel when the cooling fan stops due to a fault.
Check point
Check the cooling fan for a fault.
Corrective action
Replace the fan.