32
Input terminals
(2) Current input (4, 5, AU)
To automatically perform operation under constant pressure or temperature control
using a fan, pump etc., enter the controller output signal of 4 to 20mADC across
terminals 4-5.
Terminals AU-SD must be shorted to use the 4 to 20mADC signal for operation.
When the multi-speed signal is input, the current input is ignored.
1.4.3 External frequency selection (REX, RH, RM, RL)
Up to 15 speeds (*) may be selected for an external command forward rotation start or
up to 7 speeds for an external command reverse rotation start according to the
combination of connecting the multi-speed select terminals REX, RH, RM and RL-SD,
and multi-speed operation can be performed as shown below by shorting the start
signal terminal STF (STR)-SD.
Speeds (frequencies) may be specified as desired from the operation panel or
parameter unit as listed below.
CAUTION
• * Change the setting of Pr. 63 "STR terminal function selection" to "8", and
assign and use as the 15-speed select signal (REX).
Change the setting of Pr. 60 "AU terminal function selection" to "0", and
assign and use as the low-speed run command (RL).
Has precedence over the main speed setting signal (0 to 5V, 0 to 10V, 4 to
20mADC).
Automatic/manual
signal switching
Automatic signal
4-20mADC
AU
10
2
5
4
Inverter
OFFON
Operation
Manual operation
Frequency setting
potentiometer
Automatic
operation
4 to 20mA
Manual-Automatic Switching
Manual
operation
0 to 5V
(0 to 10V)
SD
Across
AU-SD
REX
Speed 1
(high speed)
Speed 5
Speed 6
Speed 7
Time
ON ON ON ON
RM
ONONON
RL
RH
ON ON ON ON
Output frequency (Hz)
(low speed)
Speed 3
Speed 2
(middle speed)
Speed 4
Time
Speed 9
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
ON ON ON ON
RH
ON ON ON ON
RM
ON ON ON ON
RL
ONON ON ON ON ON ON ON
REX
Output frequency (Hz)
Speed 8