Operation selection function
2
FUNCTIONS
REMARKS
If the multi-speed (RH, RM, RL signal) or jog operation (JOG signal) is entered, PID control is
stopped and multi-speed or jog operation is started.
Changing the terminal functions using Pr. 64 and Pr. 65 may affect the other functions.
Confirm the functions of the corresponding terminals before making settings.
When PID control is selected, the minimum frequency is the frequency set in the calibration
parameter C2 and the maximum frequency is the frequency set in Pr. 38.
(The Pr. 1 "maximum frequency" and Pr. 2 "minimum frequency" settings are also valid.)
When the control is switched to PID control during normal operation, the frequency command
value calculated by PID operation using 0Hz as standard is used without the frequency
during the operation.
Related parameters
X14 signal assignment Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 109)
FUP, FDN and RL signal assignment Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 111)
Voltage input selection (0 to ±5V, 0 to ±10V) Pr. 73 "0-5V/0-10V selection"
(refer to page 115)
Operation mode selection Pr. 79 "operation mode selection" (refer to page 120)
Making terminal calibration Pr. 38, Pr. 39, C2 to C7 (calibration parameters) (refer to page 92)
PID action
Frequency
command
PID set point
Frequency command
during normal operation
ON
Operation when control is switched to PID control during normal operation
Normal operation PID operation Normal operation