Omron C200HS Garage Door Opener User Manual


 
429
Data Break (Command)
The read information is specified one item at a time separated by a break code
(,). The maximum number of items that can be specified is 128. (When the PV of
a timer/counter is specified, however, the status of the Completion Flag is also
returned, and must therefore be counted as two items.)
Batch Reading
The bit, word, and timer/counter status is read as a batch according to the read
information that was registered with QQ.
Command Format
@ QQ
x 10
0
x 10
1
IR
:
Node no. Header
code
Sub-header
code
TerminatorFCS
Response Format
,
@
QQ
x 10
0
x 10
1
x 16
1
x 16
0
IR
x 16
3
x 16
2
x 16
1
x 16
0
:
ON/
OFF
x 10
3
x 10
2
x 10
1
x 10
0
ON/
OFF
Node no. Header
code
Sub-header
code
End code Timer/Counter
If PV is specified the sta-
tus of the Completion Flag
is also returned.
Data break
Bit data
ON/OFF
Word data
IR, SR, LR, HR,
AR, DM
TerminatorFCS
,,
,
Parameters Read Data (Response)
Read data is returned according to the data format and the order in which read
information was registered using QQ. If “Completion Flag” has been specified,
then bit data (ON or OFF) is returned. If “Word” has been specified, then word
data is returned. If “PV” has been specified for timers/counters, however, then
the PV is returned following the Completion Flag.
Data Break (Response)
The break code (, ) is returned between sections that are read.
11-3-34 ABORT –– XZ
Aborts the Host Link operation that is currently being processed, and then en-
ables reception of the next command. The ABORT command does not receive a
response.
Command Format
@ XZ
x 10
0
x 10
1
:
Node no. Header
code
TerminatorFCS
Host Link Commands
Section 11-3