Note The data inside the Memory Cassette should be protected by turning on the
write-protect switch whenever you are not planning to write to the Cassette.
Writing Data The following procedure is used to write IOM data from the C200HS CPU to a
Memory Cassette mounted in the CPU.
1, 2, 3...
1. Turn off the write-protect switch on the Memory Cassette to write-enable it.
2. Make sure that power to the C200HS CPU is turned OFF.
3. Mount the Memory Cassette to the CPU.
4. Turn on the CPU.
5. Switch the C200HS to PROGRAM mode.
6. Turn ON SR 27300 from the LSS or a Programming Console. The IOM data
will be written to the Memory Card and SR 27300 will be turned OFF auto-
matically.
Reading Data The following procedures are used to read IOM data from a Memory Cassette
mounted in the C200HS CPU to the CPU. This data cannot be read out automat-
ically at startup and must be read manually. Also, the error log in DM 6000 to DM
6030 cannot be read with this procedure.
1, 2, 3...
1. Make sure that power to the C200HS CPU is turned OFF.
2. Mount a Memory Cassette to the CPU.
3. Turn on the CPU.
4. Switch the C200HS to PROGRAM mode.
5. Turn ON SR 27301 from the LSS or a Programming Console. The IOM data
in the Memory Cassette will be read to the CPU and SR 27301 will be turned
OFF automatically.
IOM Area Data Section 9-4