Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 87
Type
To select the type of control module being programmed, press the 2 key while
viewing the Edit Control Screen #2. This will cause the control panel to display the
following Control Type Screens. Press the down arrow key to view additional
screens and selections.
While viewing one of the Control Type screens, select the type of control module
being programmed by pressing the corresponding keypad number key. The display
will return to the Edit Control Screen #2 and indicate the new type selection.
Note: A control relay module set to the Resettable Power type will follow the main
circuit board 24 VDC resettable power unless the control relay module is disabled.
The following table contains control module type codes and their functions which
are displayed in the Control Type screens:
Note:
1. When using a control relay module to supply resettable power to conventional 2-
wire smoke detectors, the addressable monitor module must be programmed for
Smoke-Conventional operation
2. For HVAC SHUTDN description, refer to "Control Module Operation" on page
208
Control Type Special Function
Bell Circuit NAC Type - supervised
Horn Circuit NAC Type - supervised
Sounders NAC Type - supervised
Relay Ignore Open Circuit
Strobe Circuit NAC Type - supervised
Control NAC Type - supervised
Resettable Power
1
Relay Type - Ignore Open Circuit
HVAC SHUTDN
2
Relay Type - Ignore Open Circuit
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1