Programming
70 MS-9200UDLS PN 52750:E1 01/27/09
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel
activation (including alarm relay and communicator) for a period of 15 seconds plus
a programmable time of up to 3 minutes. Zone 97, however, will activate
immediately and may be used to connect a signaling device to indicate PAS
activation (do not use a Notification Appliance Circuit for this purpose). To enable
the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display
reads PAS Yes. Each press of the 2 key will cause the display to toggle between PA S
Yes and PAS No . Refer to "Positive Alarm Sequence" on page 165.
For example, if a detector with address 005 is to be configured for PAS operation:
Select PAS Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this
example Z001
Program an output, such as a control module that is to be activated by detector
005 by assigning the same zone to it; in this example Z001
Program an output, such as a control module, for PAS activation by assigning
zone Z97 to it. This control module may be connected to a signaling device
used to indicate a PAS condition (do not use a Notification Appliance Circuit
for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay
timer to some value
With the preceding program settings, when the detector with address 005 is
activated, zone Z97 will cause its associated control module to activate
immediately, sounding the connected PAS signaling device. Following the PAS
delay time, zone Z001 will cause its associated control module to activate and the
control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a
preprogrammed time delay of up to three minutes while allowing for visual
verification by a person. Note that the alarm relay and communicator will respond
to the initial alarm immediately. In addition, Zone 98 will activate. This zone can
be programmed to a control module which may be used to activate a sounder or
indicator which the installer designates as a Presignal indication (do not use a
Notification Appliance Circuit for this purpose). To enable the Pre-signal feature,
press 3 while viewing Edit Detector Screen #3 until the display reads Pre-signal
Yes. Each press of the 3 key will cause the display to toggle between Pre-signal Yes
and Pre-signal No. Refer to "Presignal" on page 164.
For example, if a detector with address 005 is to be configured for Pre-Signal
operation:
Select Pre-signal Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this
example Z001
Program an output, such as a control module that is to be activated by detector
005 by assigning the same zone to it; in this example Z001
Program an output, such as a control module, for Pre-signal activation by
assigning zone Z98 to it. This control module may be connected to a signaling
device used to indicate a Pre-signal condition (do not use a Notification
Appliance Circuit for this purpose)