Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 141
Report Style
Pressing 3 while viewing Central Station Screen #2 will cause the Report Style display to toggle
between Point and Zone. Setting the Report Style to Point will program the DACT to report
individual point status to the Central Station. The control panel is capable of monitoring a total
of 198 addressable devices. Setting the Report Style to Zone will program the DACT to report
zone status to the Central Station. The control panel is capable of monitoring a total of 99
individual zones.
Notes:
1. Detector Address 01 will be reported to the Central Station as Point 01, Detector Address
02 as Point 02, with reports continuing in a similar fashion all the way up to Detector
Address 99 which will be reported as Point 99.
2. Module Address 01 will be reported to the Central Station as Point 160, Module Address
02 will be reported to the Central Station as Point 161, with reports continuing in a similar
fashion all the way up to Module Address 99 which will be reported as Point 258.
3.6.9.2.7 Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2
by the DACT when using an alternate means of secondary transmission path. The factory
default setting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the
following screen to be displayed:
Each press of the 1 key while viewing this screen will toggle the option between Supervise
Phone Line 2 Yes and No.
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE POINT
Central Station Screen #2
ON BOARD DACT
1=FUTURE USE
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
SUPERVISE PHONE LINE
1=PHONE LINE 2 YES
Panel ID Screen