Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 79
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit
Module Screen #2. Each press of the key will toggle the screen between Enabled
Yes and Enabled No. If Enabled No is selected, the module will not be polled by the
control panel, preventing the module from reporting alarms and troubles to the
panel. The control panel will indicate a system trouble condition and the Disable
LED with turn on if any devices are disabled.
Type Monitor
Using the PK-CD Upload/Download utility program, unique user-defined monitor
types can be created and loaded into the FACP for later use. The FACP response to
the activation of a user-defined type is the same as most previous standard types in
the list, thus allowing a variety of user-defined types and responses. To select the
type of monitor module being programmed, press the 2 key while viewing the Edit
Monitor Screen #2. This will cause the control panel to display the following
Monitor Type Screens:
Pressing the down arrow key will display additional Monitor Type screens. While
viewing one of the Monitor Type screens, select the type of monitor module being
programmed by pressing the corresponding keypad number key. The display will
return to the Edit Monitor Screen #2 which will show the new type selection.
Table 3.1 on page 80 lists the Monitor Types and their respective functions.
EDIT MONITOR
1=ENABLED
2=TYPE MONITOR
Edit Monitor Screen #2
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1