Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Operating Instructions
MS-9200UDLS PN 52750:E1 01/27/09 169
4.22.1 System Point
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be
displayed:
The operator selects the type of device which is to be viewed by pressing 1 for Detector
or 2 for Module. If 1 is pressed, the display will change to the following screen:
Entering the three digit detector address will cause the control panel to display the
current status of the selected device. For example, if a detector with address 001 on the
SLC loop is entered, a display similar to the following will appear:
The information in the preceding display includes:
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector
(could also be ION for ionization smoke detector)
NORTH CLASSROOM - the Adjective/Noun label for this device
Z005 - the first of five possible assigned software zones
1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
V - Alarm Verification Enabled (V = Yes, * = No)
S - Silenceable for control modules (S = Yes, * = No)
W - Walktestable for control and monitor modules (W = Yes, * = No)
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1
READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE
READ SYSTEM POINT
ENTER DETECTOR#
***
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Z005
V 1D001