Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
120 MS-9200UDLS PN 52750:E1 01/27/09
ANN-I/O Options
Pressing 2 for Module Options while viewing ANN-BUS Address screen when the
ANN-I/O option is selected will display the following screen:
The first screen indicates that the ANN-I/O at ANN-BUS address 1 is programmed
to annunciate SLC Loop #1 addressable Detectors with addresses 1 through 30.
The programming can be changed using ANN-I/O Address Screens 2 and 3.
Pressing 1 while viewing ANN-I/O Address Screen #2 will program the
annunciator module to annunciate either Point (addressable device address)
information or Zone information.
Pressing 1 while viewing ANN-I/O Address Screen #3 will select the Point or Zone
range to be annunciated (refer to the tables in "ANN-I/O Zone Option" on page 121
and "ANN-I/O Point Option" on page 122).
Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable
detectors or addressable modules to be annunciated.
ANN-I/O ADDR 1
LOOP1 DET 1-30
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
ANN-I/O ADDR 1
1=POINT/ZONE
ANN-I/O Address Screen #2
ANN-I/O ADDR 1
1=RANGE
2=DET/MOD
ANN-I/O Address Screen #3