Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Installation
54 MS-9200UDLS PN 52750:E1 01/27/09
2.8 Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line
control/command is made possible via double line seizure as well as usage of an RJ31X
style interconnection. Note that it is critical that the panel's digital communicator be
located as the first device on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
The control panel's digital communicator is built into the main circuit board.
Connection and wiring of two phone lines is required as shown below.
Figure 2.12 DACT Installation
Customer Premises Equipment and Wiring
Telephone
Line
FACP with DACT
Network
Service
Provider’s
Facilities
Network
Demarcation
Point
RJ31X
Jack
Unused
RJ-11 Jack
Unused
RJ-11 Jack
Telephone
Telephone
Telephone
Answering
System
Fax Machine
Computer
actadact.cdr
Figure 2.13 Wiring Phone Jacks