Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Default Programming
MS-9200UDLS PN 52750:E1 01/27/09 197
APPENDIX B Default Programming
The following table provides a list of the programming options and their factory default
settings.
Program Option Factory Default Program Option Factory Default
Detector Programming Not Installed Relay 1 Alarm
Detector Type Smoke-Photo Relay 2 Trouble (fixed)
Detector Verification Off Relay 3 Supervisory
Detector Walktest Yes Annunciator Terminal Mode No
Detector PAS No Annunciator ACS Mode No
Detector Presignal No UDACT No
Detector Zone Assign. 000 only ACS Installed No
Detector Adj/Noun none Onboard DACT No
Module Programming Not Installed Printer-PC No
Module Type Monitor Printer Baud 9600
Module Walktest Yes Service Terminal Panel ID 0000
(not used) Ring Count 0
Module Presignal No Primary Phone Type Touchtone
Module Zone Assign. 000 only Secondary Phone Type Touchtone
Module Adj/Noun none DACT Communication OFF
Zone 0 Enable Enabled AC Loss Delay 2
Zone 1 Enable Enabled Backup Reporting First Available
Zone 2 Enable Enabled Primary Reporting Style Report Point
Zone 3 Enable Enabled Secondary Reporting Style Report Point
.........................through.......... ..................... Primary Account Code 0000
Zone 96 Enable Enabled Secondary Account Code 0000
Zones 97, 98 & 99 Enabled Primary 24 Hour Test Time 0100
(future) Secondary 24 Hour Test Time 0200
Loop Style Style 4 Primary Phone Number
Loop Protocol LITESPEED Secondary Phone Number
Trouble Reminder Off Primary DACT Format Ademco Contact ID
Banner Secondary DACT Format Ademco Contact ID
Time Format 12 Hr ANN Enabled No
Hours Setting 12 ANN-BUS Modules Addr. 1 - 8 None
Minutes Setting 00 ANN-S/PG Port Parallel
Second Settings ANN-S/PG Baud 9600
AM-PM Setting AM ANN-S/PG Data Bits 7
Month Setting 01 ANN-S/PG Parity Even
Day Setting 01 ANN-S/PG Stop Bits 1
Year Setting 00 ANN-S/PG Offline Timer 60
Daylight Savings Enabled ANN-S/PG Printer Supervision No
Month Start Daylight Savings March ANN-80 Piezo Enabled Yes
Week Start Daylight Savings Week 2 ANN-80 Lock Enabled Yes
Month End Daylight Savings November ANN-80 Acknowledge Button Enabled Yes
Week End Daylight Savings Week 1 ANN-80 Silence Button Enabled Yes
Verification OFF ANN-80 Reset Button Enabled Yes
PAS Timer 0 ANN-80 Drill Button Enabled Yes
Presignal Timer 0 ANN-I/O Point/Zone Zone
Waterflow Retard Timer 0 ANN-I/O Range 00-29
NAC 1, 2, 3 & 4 Enable Enabled ANN-I/O Active LEDs Only
NAC 1, 2, 3 & 4 Silenceable Yes ANN-RLY Relay 1 Zone 1
NAC 1, 2, 3 & 4 Type Bell ................through....................... ............
NAC 1, 2, 3 & 4 Sync Type System Sensor ANN-RLY Relay 10 Zone 10
NAC 1, 2, 3 & 4 Autosilence 0 ANN-LED Point/Zone Zone
NAC 1, 2, 3 & 4 Coding Steady ANN-LED Alarms/ATS (Alarm, Trbl, Supv) ATS
NAC 1, 2, 3 & 4 Zones Zone 000 only ANN-LED Range 0 - 9
NAC 1, 2, 3 & 4 Silence Inhibit No