Product Description
40 MS-9200UDLS PN 52750:E1 01/27/09
Examples:
FACP Input programmed to Zone 33 goes into alarm, the programmed message
for Zone 33 [Message 1, 2, 3, 4 or 5] will play over the ACC-25/50ZS Series
output circuit 1 which corresponds to FACP Zone 33.
FACP Input programmed to Zone 1 and Zone 34 (Zone 1 is programmed for a
Message [1, 2, 3, 4 or 5] and Zone 34 is programmed for No Message) goes into
alarm, the programmed message for Zone 1 will play over the ACC-25/50ZS
Series output circuit 2 which corresponds to FACP Zone 34.
If two or more input zones are active at the same time, the highest priority
message will turn on (Message 1 is highest priority and Message 5 is lowest) and
play over the corresponding audio panel output circuit(s).
Zone 32 is an All-Call zone. All audio panel output circuits will turn on if Zone
32 is activated and its programmed message will play (or the highest priority
message currently being played).
A fault at the ACC-25/50ZS Series panel will cause the FACP to indicate a System
Trouble and the display will indicate a Voice Evac Fault.
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair
of communication wires connected between the A(+)/B(-) terminals on TB9 of the
FACP and TB1 terminals 2 & 3 of the ACC-ZPMK module on the audio panel.
A (+)
B (-)
FACP
ACC-ZPMK
on ACC-25/50ZS Series
Figure 1.1 FACP Connection to ACC-25/50ZS Series Audio Panel
ANN-BUS