Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
84 MS-9200UDLS PN 52750:E1 01/27/09
Description
The Description selection allows the programmer to enter additional information
about the monitor module currently being programmed. This information will be
displayed as part of the device label on the LCD display. Pressing 2 while viewing
Edit Monitor Screen #5 will cause the following screen to be displayed:
A flashing cursor will appear at the first asterisk to the left. The programmer can
enter additional descriptive information about the device being programmed. This
information will appear on the LCD display along with the standard device label
information.
A maximum of 20 characters (including spaces) can be entered. To enter
alphanumeric characters from the keypad, repeatedly press the appropriate key until
the desired character is displayed in the first position. For example, to enter the
letter B, press the 2 (ABC) key three times to toggle through the characters 2, A and
B. Press the right arrow key to move the cursor one position to the right and repeat
the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been
entered, press the Enter key to store the information. The display will return to the
Edit Monitor Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the
cursor is on the first letter of the Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the
entire Adjective field is replaced with the field entered for the previous device
programmed, and the cursor moves to the last character of the field (Recall
function). The Recalled Adjective or Noun field may now be changed letter-by-
letter
If the zero key is pressed again with no other intervening key actions and the last
character in the field is a number 0-9, the number is incremented by one. If the
last character is a letter, it changes to a 0. If the last character is 9 it goes to 0
The above increment function may be repeated with each press of the zero key
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Monitor Screen #5
DESCRIPTION 1M012
NOUN/ADJECTIVE
********************
Noun/Adjective Screen