Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
130 MS-9200UDLS PN 52750:E1 01/27/09
Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a
screen to appear which allows the user to select between No Parity, Even Parity or
Odd Parity.
Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a
screen to appear which allows the user to select between 1.0 or 2.0 Stop Bits.
3.6.9.1.3.5 ANN-80 Options
Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:
The Piezo Enable option allows the programmer to select whether the piezo sounder
on any installed ANN-80 module will ever sound. Pressing 1 while viewing the
ANN-80 Options Screen #1 causes the display to toggle between Piezo Enable Yes
and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not any
installed ANN-80 annunciator must be unlocked by its key before any annunciator
key presses will function. Pressing 2 while viewing the ANN-80 Options Screen #1
causes the display to toggle between Lock Enable Yes (annunciator must be
unlocked for keys to function) and Lock Enable No (lock position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the
programmer to select whether the Ack/Step button on any installed ANN-80
annunciator will function normally or always be ignored. Pressing 3 while viewing
the ANN-80 Options Screen #1 causes the display to toggle between Ack Btn
Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step
button never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to
select whether the Silence button on any installed ANN-80 annunciator will
function normally or always be ignored. Pressing 1 while viewing the ANN-80
Options Screen #2 causes the display to toggle between Sil Btn Enable Yes (Silence
button functions normally) and Sil Btn Enable No (Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to
select whether the Reset button on any installed ANN-80 annunciator will function
normally or always be ignored. Pressing 2 while viewing the ANN-80 Options
Screen #2 causes the display to toggle between Rst Btn Enable Yes (Reset button
functions normally) and Rst Btn Enable No (Reset button never functions).
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2