Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Central Station Communications
MS-9200UDLS PN 52750:E1 01/27/09 183
The table below shows UL listed receivers which are compatible with the MS-9200UDLS.
1. With 685-8 Line Card with Rev. 4.4d software
2. With 124060V206B and 124063 Line Card Rev. B
3. With version V2.4 Receiver and 126047 Line Card Rev. G
4. With 124077V2.00 Receiver and 126047 Line Card Rev. M
5. With V.7301 Receiver S/W
6. With 01.01.03 Receiver S/W and Line Card 01.01.03
7. With software V1.86
8. With software V1.72
9. With DSP4016 and V1.6 Line Card
10. With software V3.9
IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm Communicator/
Transmitter is compatible with the Central Station Receiver, utilized by the monitoring service,
prior to installation. The Compatibility Table provides a list of compatible receivers and associated
software versions for the receivers. Changes in the hardware and/or software by the receiver
manufacturers may affect the receiver compatibility with the FACP DACT. After completing the
installation, communication between the DACT and Central Station Receiver must be tested and
verified.
Table 5.1 Compatible UL Listed Receivers
Format
Ademco
685 (1)
Ademco
MX8000 (2)
Silent Knight
9500 (3)
Silent Knight
9800 (4)
Osborne Hoffman
2000E (5)
Radionics
6600 (6)
SurGard
MLR2 (7)
SurGard
System III (8)
SurGard
MLR-2000 (9)
FBI
CP220FB (10)
0 SIA-DCS-8

1 SIA-DCS-20

2 Ademco Contact ID
