Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
152 MS-9200UDLS PN 52750:E1 01/27/09
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a
screen similar to one of the following two screens to be displayed:
If there are no events in the current walktest session, the first screen will be displayed,
indicating no events have been stored in the walktest log. If any events have been
stored, a screen similar to the second will be displayed indicating the latest event. As
walktest events occur, the display will change to indicate the latest event. All stored
events can be scrolled on the screen by pressing the up or down arrow keys. To return
to the first event, press the 1st Event key.
Pressing 2 for View Points while viewing the Unit In Walktest screen will display one
of the following screens:
If the system has no points installed, the first screen will be displayed. If points are
installed, the second screen will be displayed, which allows the viewing of all untested
system points and their status relating to the current walktest session. The up and down
arrow keys will allow viewing of all untested points. If a point is tested while it is being
displayed, the screen will update and display the next untested point. The first line
indicates the total number of untested points. The second line displays information
about an untested point. A description on the bottom of the screen will indicate if the
displayed point has been disabled, if the Walktest option has been disabled for that
point or if the point is not yet tested. The up and down arrow keys allow the user to
scroll through all untested points.
Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a
new screen which will show a total of the tested detectors, tested modules, untested
detectors and untested modules for the current walktest session.
To end the Walktest session, press the Escape key to return to the Walktest screen.
Pressing 3 for View Results while viewing the Walktest screen, after a walktest session
has been completed, will allow the operator to view the final results of the most recent
walktest.
NO EVENTS IN
WALKTEST LOG
OR
ALARM: MONITOR
NORTH CLASSROOM
Z001
10*15A 012308 1M006
NO POINTS IN
SYSTEM
OR
UNTESTED POINTS 010
1D001 SMOKE (PHOTO)
*********************
NOT TESTED