Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 113
3.6.8 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset
the control panel after each device activation. Pressing 2 while viewing the
Programming Screen #3 will cause the following Walktest options to be displayed:
To perform a silent walktest which will not sound the NACs, press 1 while viewing the
Walktest Screen. To perform an audible walktest, which will sound the NACs, press 2
while viewing the Walktest Screen. When either option is chosen, the panel will enter
Walktest Mode and the following screen will be displayed::
From this screen, it is possible to view the walktest log, untested system points or a
summary of the addressable devices tested during the current walktest. The user can
select between any of these screens without interrupting the current walktest session.
The walktest session will not end until the Unit In Walktest screen is exited by pressing
the Escape key.
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a
screen similar to one of the following two screens to be displayed:
If there are no events in the current walktest session, the first screen will be displayed,
indicating no events have been stored in the walktest log. If any events have been
stored, a screen similar to the second will be displayed indicating the latest event. As
walktest events occur, the display will change to indicate the latest event. All stored
events can be scrolled on the screen by pressing the up or down arrow keys. To return
to the first event, press the 1st Event key.
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
Unit In Walktest Screen
NO EVENTS IN
WALKTEST LOG
ALARM: MONITOR
NORTH CLASSROOM
Z001
10*15A 012308 1M006
OR