1.8.5 Battery Charger
1.8.5.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-
9200UDLS FACP. The FACP battery charger must be disabled, by removing
jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be
housed in the BB-26 battery box. Larger batteries and the charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the CHG-75 Manual for additional information.
1.8.5.2 CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the
MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing
jumper JP5, when using the CHG-120F. The batteries and charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Note that when using the BB-55F for housing the charger and batteries
greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual
for additional information.
1.8.6 IPDACT- Internet Protocol DACT
The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter
designed to allow FACP status communication to a Central Station via the internet. No
telephone lines are required when using the IPDACT. Using Contact ID protocol from
the FACP, the IPDACT converts the standard DACT phone communication to a
protocol that can be transmitted and received via the internet. It also checks
connectivity between the FACP and Central Station. Refer to the IPDACT Product
Installation Document P/N 53109 for additional information.