1.8.7.4.2.1 Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote
printer requires a secondary power source (battery backup). Since a secondary
power source is not provided as a standard feature, a separate UL-listed
Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of
NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard
DB-25 cable. One end of the cable will plug into the DB-25 connector on the PRN
printer and the other end plugs into the parallel connector on the ANN-S/PG
module. Note that the 9-pin DB-9 port on the ANN-S/PG is used to connect a serial
printer. The 25-pin port is used for a Centronics parallel printer cable. Connect
either a serial or parallel printer, but not both at the same time.
1.8.7.4.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on
using the printer menu controls. Set the printer options (under the menu area) as
shown in the following table:
Table 1.2 PRN Setup Options
Option Setting Option Setting
Font HS Draft CPI 10CPI
LPI 6 LPI Skip 0.5
ESC Character ESC Emulate Epson FX-850
Bidirectional Copy ON I/O
CG-TAB Graphic Buffer 40K
Country E-US ASCII Serial
Auto CR OFF Baud 9600 or 2400
Color Option Not Installed Format 7 Bit, Even, 1 Stop
Formien Protocol XON/XOFF
Lines 6LPI=60 Character Set Standard
Standard Exec 10.5 SI.Zero On
Auto LF On
PAPER
BIN 1 12/72”
BIN 2 12/72”
SINGLE 12/72”
PUSH TRA 12/72”
PULL TRA 12/72”
PAP ROLL 12/72”