3.6.5.4.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-
signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press
2 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay
time consisting of three digits, such as 009 for nine seconds. Upon entering the
third digit, the time delay will be stored in the control panel memory and the display
will return to the Delay Screen which will indicate the new delay time.
Note that the FACP allows programming for PAS and Pre-signal timers, but a
detector can only be programmed for either PAS or Pre-signal operation. Refer to
"Edit Detector" on page 66 for programming details.
3.6.5.4.3 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to
include any built-in delays of the waterflow device. The factory default setting for
Waterflow delay is 000 for no delay. To select a Waterflow delay of 01 to 90
seconds for all devices programmed for Waterflow delay, press 3 while viewing
Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay
time consisting of two digits, such as 25 for twenty-five seconds. Upon entering the
second digit, the time delay will be stored in the control panel memory and the
display will return to the Delay Screen which will indicate the new delay time.
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
TIMER
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
Timer Screen #1
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen