Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Power Supply Calculations
MS-9200UDLS PN 52750:E1 01/27/09 189
Table 7.3 contains columns for calculating current draws. For each column, calculate the current
and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 7.4 on page 190.
Table 7.3 System Current Draw Calculations
Device Type
Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)
Calculation Column 2
Primary, Fire Alarm Current
(amps)
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Qty X[current draw]= Total Qty X [current draw] = Total Qty X[current draw]= Total
Main Circuit Board 1 X[0.340]= 0.340 1 X[0.360]= 0.360 1 X[0.137]= 0.137
ANN-80 [ ] X[0.037]= [ ] X[0.040]= [ ] X[0.015]=
ANN-LED [ ] X[0.028]= [ ] X[0.068]= [ ] X[0.028]=
ANN-RLY [ ] X[0.015]= [ ] X[0.075]= [ ] X[0.015]=
ANN-I/O [ ] X[0.035]= [ ] X[0.200]= [ ] X[0.035]=
ANN-S/PG [ ] X[0.045]= [ ] X[0.045]= [ ] X[0.045]=
ACM-8RF [ ] X[0.030]= [ ]
X[0.158]
1
=
[ ] X[0.030]=
ACM-16ATF
ACM-32AF
[ ] X[0.040]= [ ]
X[0.056]
2
=
[ ] X[0.040]=
AEM-16ATF
AEM-32AF
[ ] X[0.002]= [ ]
X[0.018]
2
=
[ ] X[0.002]=
AFM-16ATF
AFM-32AF
[ ] X[0.040]= [ ]
X[0.056]
2
=
[ ] X[0.040]=
AFM-16AF [ ] X[0.025]= [ ]
X[0.065]
2
=
[ ] X[0.025]=
LDM-32F [ ] X[0.040]= [ ]
X[0.056]
3
=
[ ] X[0.040]=
LDM-E32F [ ] X[0.002]= [ ] X[0.018]= [ ] X[0.002]=
LCD-80F [ ] X[0.064]= [ ] X[0.064]= [ ] X[0.025]=
4XTMF [ ] X[0.005]= [ ]
X[0.011]
4
=
[ ] X[0.005]=
4-wire Detector Heads [ ]
X[ ]
5
=
[ ] X[ ]= [ ] X[ ]=
Power Supervision
Relays
6
[ ] X[0.025]= [ ] X[0.025]= [ ] X[0.025]=
CP350 & CP355 [ ] X[0.00030]=
maximum alarm draw
for all devices 0.400
[ ] X[0.00030]=
SD350 & SD355 [ ] X[0.00030]= [ ] X[0.00030]=
SD350T & SD355T [ ] X[0.00030]= [ ] X[0.00030]=
AD350 & AD355 [ ] X[0.00030]= [ ] X[0.00030]=
H350 & H355 [ ] X[0.00030]= [ ] X[0.00030]=
H350R & H355R [ ] X[0.00030]= [ ] X[0.00030]=
H355HT [ ] X[0.00030]= [ ] X[0.00030]=
D350P & D350PL [ ] X[0.00030]= [ ] X[0.00030]=
D350RP & D350RPL [ ] X[0.00030]= [ ] X[0.00030]=
B501BH & B501BHT
7
[ ] X[0.001]= [ ] X[0.001]=
B224RB Relay Base [ ] X[0.00050 ]= [ ] X[0.00050 ]=
B224BI Isolator Base [ ] X[0.00045]= [ ] X[0.00045 ]=
MMF-300 [ ] X[0.00040]= [ ] X[0.00040]=
MMF-300-10 [ ] X[0.00350]= [ ] X[0.00350]=
MDF-300 [ ] X[0.00075]= [ ] X[0.00075]=
MMF-301 [ ] X[0.000375]= [ ] X[0.000375]=
MMF-302 [ ] X[0.00027]= [ ] X[0.00027]=
MMF-302-6 [ ] X[0.00200]= [ ] X[0.00200]=
BG-12LX [ ] X[0.00030]= [ ] X[0.00030]=
CMF-300 [ ] X[0.00039]= [ ] X[0.00039]=
CMF-300-6 [ ] X[0.00225]= [ ] X[0.00225]=
CRF-300 [ ] X[0.00027]= [ ] X[0.00027]=
CRF-300-6 [ ] X[0.00145]= [ ] X[0.00145]=
I300 [ ] X[0.00040]= [ ] X[0.00040]=
NAC #1
8
[ ] X[ ]=
NAC #2 [ ] X[ ]=
NAC #3 [ ] X[ ]=
NAC #4 [ ] X[ ]=
Current Draw from TB3
(nonalarm
9
)
[ ]= [ ] [ ]= [ ] [ ]=
Sum each column
10
for totals Primary Non-Alarm = Primary Alarm = Secondary Non-Alarm =
Table Footnote
1. All eight ACM-8RF relays activated on a single module.
2. All annunciator LEDs on
3. LDM-32F with LEDs on
4. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
5. Refer to the Device Compatibility Document for standby current.
6. Must use compatible listed Power Supervision Relay.
7. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
8. Current limitation of Terminal TB3 & TB4 circuits is 2.5 amps per NAC.
9. The total standby current must include both the nonresettable/resettable (TB1 Terminals 1 & 2) and resettable
(TB1 Terminals 3 & 4) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified. Current limitations of TB3 & TB4 circuits is 2.5 amps per
NAC output and 0.3 amps per special application auxiliary power output
10.Total current draw listed above cannot exceed 6.0 amps.