Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Product Description
MS-9200UDLS PN 52750:E1 01/27/09 31
1.8.7.4 ANN-S/PG Serial/Parallel Interface Installation
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote
serial or parallel printer to the FACP for a real-time log of system events, detector
status reports and event history. The module is provided with a plastic enclosure for
surface mounting. Proceed with the installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.6
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID
number (address) to the module
4. Select the address and configuration options for the ANN-S/PG module as
described in the Programming section of this manual (refer to "ANN-BUS
Options" on page 118)
Note that the Auto-configure feature allows the programmer to quickly bring all
installed ANN-BUS modules online (refer to "Auto-Configure" on page 128)
5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure
1.6). Only one printer can be connected.
1.8.7.4.1 Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
1.8.7.4.2 PRN-6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the
status changes within the control panel and time-stamps the printout with the time
of day and date that the event occurred. It provides 80 columns of data on standard
9” x 11” tractor-feed paper. This section contains information on connecting a
printer to the control panel and setting the printer options.
Figure 1.6 ANN-S/PG Connection to FACP
ANN-S/PG Module
MS-9200UDLS
Cable Connectors for
connection to printer
Parallel
Serial
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
ANN-BUS/ACS BUS
92udlstospg.cdr