1.8.8 Legacy ACS Series LED Zone Type Annunciators
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are
being used due to incompatible serial communication protocols.
The legacy ACS Series Annunciators remotely display alarm and trouble status as well
as system status. In addition, they can provide remote Acknowledge, Silence, Reset
and Drill functions. For more detailed information, refer to the appropriate annunciator
manual. Following is a list of annunciators which can be used with the MS-
9200UDLS.
ACM-16ATF
*
Annunciator Control Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder.
AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs
ACM-32AF
*
Annunciator Control Module annunciates 32 alarm zones with 32
red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED
and a local piezo sounder. It also has a switch for local piezo silence.
AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32
red LEDs
* In Canada, the color red must be used to indicate active alarm inputs. Yellow
indicates supervisory, burglary or trouble signals. Green indicates the presence of
power, or an activated output.
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is an 80-character backlit LCD remote fire annunciator that
is capable of displaying English language text. Communications between the control
panel and the annunciator is accomplished over a serial interface employing the EIA-
485 communication standard. Up to 32 LCD-80F annunciators may be connected to
the EIA-485 circuit. The annunciators may be powered from the host FACP or a
remote UL listed filtered power supply such as the FCPS Series. For more detailed
information, refer to the LCD-80F manual.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and
LDM-E32F expander modules, are used to provide an interface to a custom graphic
LED annunciator.
Legacy ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps.
1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS-
9200UDLS on-line:
Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page
45)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to "Autoprogram" on page 64)
Resolve Programming Conflicts
Go to Point Program to Enter Specific Data (refer to "Point Program" on page
65). Use the right and left arrow keys to navigate between devices.