Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
116 MS-9200UDLS PN 52750:E1 01/27/09
3.6.9.1.2 ACS Options
Pressing 2 for ACS Options while viewing the Annunciators screen, will display the
following screen:
Pressing 1 while viewing the ACS Options screen will cause the display to toggle
between ACS Enabled Yes and ACS Enabled No. To install an ACS annunciator, the
display must read ACS Enabled Yes.
If ACS has been enabled, press 2 while viewing the Annunciator Screen to select
addresses for the ACS annunciators. The following screen will be displayed:
Pressing the down arrow key will allow the programmer to view additional screens
displaying Addresses 1 -31. Each screen will indicate if an address has been used
for an installed ACS annunciator. To select one or more addresses for the installed
ACS annunciator(s), press the number key corresponding to the address in each
screen. The display for the selected address will change from No to Yes. Each press
of the number key will cause the display to toggle between No and Yes. The address
of each installed annunciator must be enabled to allow communication between the
FACP and annunciator.
ANNUNCIATORS
1=TERM ENABLED
2=ACS OPTIONS
3=ANN-BUS OPTIONS
ACS OPTIONS
1=ACS ENABLED NO
2=ACS INSTALLED
ANNUNCIATOR
1=ADDRESS 1 YES
2=ADDRESS 2 NO
3=ADDRESS 3 NO
ACS Installed Screen