Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 71
Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre-
signal delay timer to some value
With the preceding program settings, when the detector with address 005 is
activated, zone Z98 will cause its associated control module to activate
immediately, sounding the connected signaling device to indicate the Pre-signal
condition. Following the Pre-signal delay time, zone Z001 will cause its associated
control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both
Zone Assignment
A maximum of five zones can be programmed to each addressable detector.
Pressing 1 while viewing Edit Detector Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The
factory default for an unprogrammed device is Z00 for general alarm zone. A
flashing cursor will appear on the first 0 to the left. Enter the two digit number
corresponding to the zone that is to be assigned to this device. The cursor moves to
the next Z** designation. Continue entering zone assignments or the remaining
zones can be left blank or programmed as general alarm zone Z00. When all
desired changes have been made, press the Enter key to store the zone assignments.
The display will return to the Edit Detector Screen #4. Note that the left and right
arrow keys can be used to navigate through the zones and the CLEAR key can be
used to quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors
about the detector currently being programmed. Pressing 1 while viewing Edit
Detector Screen #5 will cause the following screen to be displayed:
EDIT DETECTOR
1=ZONE ASSIGNMENT
00 ** ** ** **
Edit Detector Screen #4
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Assignment Screen
See Page
EDIT DETECTOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Detector Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen