Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Programming
MS-9200UDLS PN 52750:E1 01/27/09 107
3.6.5.5.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit
board silenceable notification appliances after a programmed length of time. To
enable this feature and program the time delay before Auto Silence activation, press
1 while viewing NAC Screen #2. The following screens will be displayed:
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence
Screen #1. To enable the Auto Silence feature, press the number corresponding to
the time delay which will elapse before Auto Silence activates. This information
will be stored in memory and the display will return to NAC Screen #2.
Note: All silenceable control modules as well as the remote power supply sync will
be controlled by the Autosilence timer for NAC 1.
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type)
The Coding feature allows the programmer to select the type of output that the main
circuit board notification appliances will generate when activated. Pressing 2 while
viewing NAC Screen #2 will cause the following displays to appear:
NAC #
1=AUTO SILENCE
2=CODING
TEMPORAL
NAC Screen #2
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2