Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Product Description
14 MS-9200UDLS PN 52750:E1 01/27/09
SECTION 1 Product Description
The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and
DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This
compact, cost effective, intelligent addressable control panel has an extensive list of
powerful features.The combination of Fire-Lite’s newer series devices and legacy 300
Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection
technology. The power supply and all electronics are contained on a single circuit
board housed in a metal cabinet, providing a complete fire control system for most
applications. Optional modules, which plug into the main circuit board, are available
for special functions. Available accessories include LED, graphic and LCD
annunciators, reverse polarity/city box transmitter, local and remote upload/download
software and remote power expansion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central
Station via the public switched telephone network. It also allows remote programming
or interrogation of the control panel using the PS-Tools Upload/Download utility via
the public switched telephone network. Local programming and interrogation is also
possible using the PS-Tools and the USB port (J12) on the FACP. Any personal
computer with Windows
XP or greater, and compatible modem with a speed of 2400
baud or faster and PS-Tools software may serve as a Service Terminal. This allows
download of the entire program or upload of the entire program, history file, walktest
data, current status and system voltages.
MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS (120 VAC
version) and the MS-9200UDLSE (240 VAC version) FACPs.
Inventory
When MS-9200UDLS shipment is received, check that all parts have been included in
shipment. The MS-9200UDLS shipment consists of one of each of the following:
main circuit board with display
backbox with door
plastic bag containing screws, cables, key, etc.
manual
1.1 Features and Options
New LiteSpeed™ polling protocol for faster SLC response time
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted,
unshielded wire (refer to "Wire Requirements" on page 205)
Built-in DACT (Digital Alarm Communicator/Transmitter)
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
198 addressable device capacity (99 detectors and 99 control/relay/monitor
modules)
99 software zones
Onboard NACs (Notification Appliance Circuits) which can be configured as
four Style Y (Class B) or two Style Z (Class A) circuits - special application
3.0 amps total power for NACs and 24 VDC special application auxiliary power
outputs expandable to 6.0 amps
3.6 amps total system power (includes battery charger) expandable to 6.6 amps
Two programmable relay outputs and one fixed trouble relay
Synchronization output for remote power supply applications (special
application)
Built-in Programmer
Telephone Line Active LEDs