Honeywell MS-9200UDLS Smoke Alarm User Manual


 
Power Supply Calculations
MS-9200UDLS PN 52750:E1 01/27/09 187
SECTION 7 Power Supply Calculations
7.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
7.2 Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run
continuously, without any disconnect devices, from the power source to the control panel.
Overcurrent protection for this circuit must comply with Article 760 of the National Electrical
Codes as well as local codes. Use 14 AWG (2.00 mm
2
) wire with 600 volt insulation for this
branch circuit.
Use Table 7.1 , to determine the total amount of current, in AC amperes (A), that must be supplied
to the system.
Table 7.1 AC Branch Circuit Requirements
Device Type
Number of
Devices
Current Draw
(AC amps)
Total Current
per Device
MS-9200UDLS
or
MS-9200UDLSE
1X
3.00
or
1.50
=
CHG-75 [ ] X 2.05 =
CHG-120F [ ] X 2.00 =
[ ] X [ ] =
Sum Column for AC Branch Current Required =