Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
Specifications
i
Notice!
When a local relay is programmed for trouble it is energized in the normal state. This causes
the common and normally-open terminals to be shorted when not in the trouble condition.
Electrical
Power (Input): 120 V 60 Hz or 220 V 50 Hz, 2.2 A
Power (Auxiliary): 24 VDC nominal, unfiltered, 1.0 A
Power (Initiating Circuit [Smoke])
1
: 24 VDC nominal, filtered, 1.0 A.
Power (Option Bus): 12 VDC nominal, 500 mA
Power (Notification Appliance Circuit
[NAC])
2
:
Each NAC has 24 VDC nominal, unfiltered
power with up to 2.5 A capacity (but limited
by overall 4.0 A capacity)
Power (Optional Standby Batteries): Two 12 V (in series), 7 Ah to 40 Ah
1
For compatible smoke detection devices, see also the FPD‑7024 Smoke Detector
Compatibility List.
2
For compatible NAC devices, see also the FPD‑7024 NAC Compatibility List
Environmental
Temperature (operating and storage):
+32°F to +120°F (0°C to +49°C)
Notification Appliance Circuits (NACs)
Wiring:
standard Class B, Style Y or Class A, Style Z as needed.
Notification patterns: Configurable for steady, pulsing, California March, ANSI code 3,
synchronized Wheelock, synchronized Gentex, and synchronized
System Sensor.
Relays
Local (on-board):
The main control panel includes Three Form “C” relays. The relay
contacts are rated at 5 A, 28 VDC. No over existing limiting is
performed on the contacts of these relays. The default selection
for the relays is to indicate general alarm and general system
trouble and supervisory. By using point or zone mapping, they
can be programmed to activate in a wide variety of conditions.
Remote
1
: Eight Form C relay outputs are provided by a D7035 Remote
Relay Module. The module connects to the FPD‑7024 through the
option bus. The outputs are fully programmable, exactly as the
local relays are programmed. Each output operates independently
of the other seven to provide complete flexibility. Communication
with the D7035 is supervised.
Contact Rating: 5 A at 28 VDC
Number of Modules: two units maximum.
1
For wiring requirements, see Option bus wiring requirements, 34.
9
98 en | Specifications Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.