Programming
Danger!
Untested systems!
After any programming change, and especially after remote programming changes, completely
check the operation of the control panel. Hazards to life and property can result if the system
is not tested to detect possible improper programming.
DANGER!
!
Warning!
Improper system operation!
When programming the system, enter only valid types of information within the ranges speci-
fied in the programming table. Incorrect programming results in improper system operation.
When using built-in programming, invalid input values might not be rejected in every case. En-
sure that you enter only the intended values while programming to prevent improper system
operation.
Programming features
For UL864 programming requirements, see the following table:
Program feature or
option
Permitted in UL864
(Yes/No)
Possible settings Settings permitted in
UL864
Auto Test Frequency Yes 4 HOURS
12 HOURS
24 HOURS
7 DAYS
28 DAYS
4 HOURS
12 HOURS
24 HOURS
Program Relay Yes Release on Trouble
Activate on Ground
Start
Release on Trouble
AC Fail Delay Yes Wait for DC
Wait Delay Time
0‑24 HRS
Wait Delay Time
1‑3 HRS
Phone Line Monitor
for Each Line
Yes No
Yes
Yes
Remote Programming
(offsite)
Yes PHONE #1
PHONE #2
COMPTR PHONE
Phone #1
Phone #2
Response Time Yes Fast (.5 sec)
Programmed
1 sec
7
7.1
Fire Alarm Control Panels Programming | en 49
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458