AC Fault: When activating, the control panel waits for the AC Delay Timer to expire
before indicating or sending a trouble condition. When the timer expires, it shows an AC
Fault on the control panel and the trouble LED turns on.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG FUNCTION options.
Press [0/Prog] to select CONFIGURE. The following window appears:
ACTVTN TYPE ( )
1- FIRE
2- WATERFLOW
3-SUPERVISORY
4- (reserved)
5- RESET
6- SILENCE
7- AC FAULT
Press the number key that corresponds to your selection. (The existing setting is shown in
parentheses on the first line.) The previous window appears.
Local only
Shortcut: 0-PROG, 4-PROG INPUTS, 2-POINT FUNCTION
Enabling this feature provides the input point for local annunciation only, with no
communicator report. Enter the point number you wish to program and press [#/Enter]. The
display scrolls through the PROG FUNCTION options.
Press [1] to select LOCAL ONLY. The following window appears:
LOCAL ONLY
_______: YES (1)NO(0)
Press either [1] to enable or [0/Prog] to disable. The previous window appears.
Silencing
Shortcut: 0-PROG, 4-PROG INPUTS, 2-POINT FUNCTION
This feature determines if an output zone (1 to 50) follows the Silence button (relays reset,
NACs silence).
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG FUNCTION options.
Press [3] to select SILENCEABLE. The following window appears:
SILENCABLE? (FF)
_______: YES (1)NO(0)
Press [1] for relays to reset and NACs to silence when the Silence button is pressed, or press
[0/Prog] for relays to remain latched until reset and NACs to continue sounding when the
Silence button is pressed.
i
Notice!
When an output is assigned to more than one zone, the programming of the zone that triggers
the output controls the output. When more than one zone triggers the output, if one of the
zones is programmed as non-silencing, the output will be non-silencing.
NOTICE!
The previous window appears. FF indicates the function being programmed.
Fire Alarm Control Panels Control Panel Programming | en 71