Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
Pressing [Drill] retrieves the next point. For instance, if you are programming Point 2 and you
press [Drill], you retrieve the setting for Point 3.
Pressing [History] retrieves the previous point. For instance, if you are programming Point 2
and you press [History], you return to the setting for Point 1.
Assigning point functions
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
This feature assigns each point to one point function. A point function is a set of
characteristics that you can assign to selected points. There are 16 point functions to choose
from.
For more information about point functions, see Point function, 70. For the limitations when
assigning points to point functions that were programmed with a response time other than
Fast, see Loop response, 72.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [0/Prog] to select FUNCTION. The following window appears:
POINT FUNC. (___)
(01 - 16):_______
Enter the function number you wish to assign to the point and press [#/Enter]. The existing
setting is shown in parentheses on the first line. After you assign a point function, the previous
window appears.
Alarm/Trouble status
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
This feature allows you to program the system response to an open loop condition. A shorted
loop always causes an alarm condition.
For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
ALARM: A point in an open circuit state causes an alarm.
TROUBLE: If a point is in an open circuit state, the system responds with a trouble condition.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [1] to select ALARM/TROUBLE. The following window appears:
OPEN STATUS (__)
1- ALARM
2- TROUBLE
Press [1] to select ALARM on open loop and ALARM on shorted loop or [2] to select TROUBLE
on open loop and ALARM on shorted loop. The previous window appears. The existing setting
is shown in parentheses on the first line.
Output zones
Shortcut: 0-
PROG, 4-PROG INPUTS, 1-POINT NUMBER
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [2] to select OUTPUT ZONE. The following window appears:
68
en | Control Panel Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.