BFSK
Similar to the programming of system events for 4/2 formats, five system events can be
programmed for two unique digits each when the BFSK format is used. This programming is
done under
7- PROG FORMATS, 3- BFSK RPT CODS.
The BFSK format supports only a three-digit account number. The control panel sends the first
three digits that are programmed. The BFSK (and tone burst) format requires that an A (hex
character) be entered at the control panel to cause the receiver to display 0. The BFSK format
can report only eight points, so Points 8 to 255 are all reported as point “8”.
SIA
The SIA reports are fixed, and do not require programming.
Contact ID
The Contact ID reports are fixed and do not require programming.
3/1
The 3/1 reporting codes are determined by the programming of the 4/2 codes. Send only
Digit 1 (left digit of the two-digit code) and the first three digits of the account number.
Modem IIIa
2
The Modem IIIa
2
reports are fixed and do not require programming.
54 en | Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.