Default Values Alternate Default
3/1
BFSK
SIA
Contact ID
4/2
digit 1
4/2
digit 2
4/2
digit 1
4/2
digit 2
POINT SUPERVISORY
DISABLE
14 see #12 p see #12 p see #12 Fz FBz 1 571 00 zzz
POINT MONITOR
DISABLE
15 see #12 p see #12 p see #12 Fz FBz 1 571 00 zzz
POINT FIRE ALARM
RESTORE
16 3 p 2 p 3 Ez FRz 3 110 00 zzz
POINT WATERFLOW
RESTORE
17 see #16 P see #16 P see #16 Ez SHz 3 113 00 zzz
POINT SUPERVISORY
RESTORE
18 see #16 P see #16 P see #16 Ez SRz 3 200 00 zzz
POINT MONITOR
RESTORE
19 see #16 p see #16 p see #16 Ez URz 3 140 00 zzz
POINT FIRE TROUBLE
RESTORE
20 3 p 7 p 3 Ez FJz 3 373 00 zzz
POINT WATERFLOW
TROUBLE RESTORE
21 see #20 p see #20 p see #20 Ez SJz 3 373 00 zzz
POINT SUPERVISORY
TROUBLE RESTORE
22 see #20 p see #20 p see #20 Ez SJz 3 373 00 zzz
POINT MONITOR
TROUBLE RESTORE
23 see #20 p see #20 p see #20 Ez UJz 3 373 00 zzz
POINT FIRE DIRTY 24 see #20 p see #20 p see #20 Ez FJz 3 385 00 zzz
POINT WATERFLOW
DIRTY RESTORE
25 see #20 p see #20 p see #20 Ez FJz 3 385 00 zzz
POINT SUPERVISORY
DIRTY RESTORE
26 see #20 p see #20 p see #20 Ez FJz 3 385 00 zzz
POINT MONITOR
DIRTY RESTORE
27 see #20 p see #20 p see #20 Ez UJz 3 373 00 zzz
POINT FIRE DISABLE
RESTORE
28 3 p 2 p A Ez FHz 3 571 00 zzz
POINT WATERFLOW
DISABLE RESTORE
29 see #28 p see #28 p see #28 Ez FHz 3 571 00 zzz
POINT SUPERVISORY
DISABLE RESTORE
30 see #28 p see #28 p see #28 Ez FHz 3 571 00 zzz
POINT MONITOR
DISABLE RESTORE
31 see #28 p see #28 p see #28 Ez FHz 3 571 00 zzz
SYSTEM IN TEST 40 F 1 3 3 F FD TS0 1 607 00
000
Fire Alarm Control Panels Appendices | en 103
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458